banner1

EPS Fire Fighting Equipment Single Phase2kVA Emergency Power Supply

EPS Fire Fighting Equipment Single Phase2kVA Emergency Power Supply

short description:

Model NO.:GHS-2KVA

Phase:Single Phase

Type:Standby

Protection:Unbalanced Loads

Application:Fire Safety

Classification:Lighting

Standby Time:Long-acting Machine

Output Capacity:Small Type

Brand:WHEG

Battery Time:90mins

Transport Package:Standard Export Carton

Specification:600*400*1200

Origin:Wenzhou China


Product Detail

Product Tags

The single-phase EPS emergency power supply adopts a backup working mode and is an emergency power supply device that provides centralized power supply for emergency evacuation lighting or important electrical equipment in a building. When the mains power is normal, the mains supplies power to the load through the mutual input device, and the charger intelligently charges the backup battery. When the mains power fails or exceeds 20% of the normal voltage, the intelligent EPS control system quickly switches the load to the inverter, and the battery continues to supply power to the load after being inverted. When the mains voltage is normal, the emergency power supply will automatically restore the .power supply to the grid.

Product Description

capacity

0.5kw

1kw

1.5kW

2kW

3kW

Charger

Charger input voltage

AC 220V(176V~240V), 50Hz±3Hz

Charging voltage

DC24V

DV48V

Charging current

0.3A/5A

Battery

Rated voltage

DC24V

DC48V

starting voltage

DC24V

DC48V

Charging time

<22h

Emergency Inverter

emergency output

AC220V±3%, 50Hz±1Hz

Output wave

Sine wave, THD≤5%(resistant)

Overload capacity

120% 30s; 150% 10s

protection function

overload, short circuit, under voltage protection

emergency switching

<5s(0.2s can be design)

Display LCD
Noise  no noise in mains mode,<55dB in emergency supply time
Relative humidity 0-90%,nocondensing
Temperature  -24ºC-40ºC
Altitude <2500M

Application
1.Traffic system
2.Industrial equipment
3.Steel factory
4.Fire fighting equipment

Main feature
1.Wide input voltage range     2.Digital control technology
3.High IP level, applied to harsh grid conditions and generators
4.Overload ability,strong anti-interference ability
5.Human nature of network management

Product Information

Product name: EPS fifire emergency power supply
Color: support customization
Applicable places: the building contains emergency control systems etc.
Installation form: flfloor type, split type, built-in type, wall-mounted type.